4LCY Lead-Calcium / 4LY Lead-Antimony
For telecommunications applications
Capacities from 290 to 660 Ampere-hours

FEATURES AND BENEFITS
 

  • Four-cell design offers reduced length for optimum space utilization
    (shorter racks)
  • Fewer bolted connectors per battery string reduce installation and maintenance costs
  • Flame-retardant covers enhance battery plant safety
  • Suspended positive plate permits free growth without pressure on jar and cover
  • Snap-on, intercell-connector insulating covers
  • Terminals accessible for measurement of individual cell voltages
  • Vacuum-assisted, bottom-pour, positive-grid casting assures plate quality and long life
  • Soft rubber post seal minimizes stress on post
 


 

SPECIFICATIONS
Plates
Height
Width
Thickness
Positive
Negative
Outside negative

15 in (381 mm)
15 in (381 mm)
15 in (381 mm)

12 in (305 mm)
12 in (305 mm)
12 in (305 mm)

0.250 in (6.4 mm)
0.180 in (4.6 mm)
0.130 in (3.3 mm)

Electrolyte height above plates 2.88 in (73 mm)
Sediment space 0.63 in (16 mm)
Electrolyte @ 77F (25C) Sulfuric acid, 1.215 specific gravity nominal
Float voltages 2.19-2.21 volts per cell (calcium); 2.15-2.17 volts per cell (antimony)
Container Thermoplastic, transparent, polycarb and SAN standard
Cover High-impact, flame-retardant thermoplastic with tongue-and-groove seal.
Flammability ratings: UL 94-VO; ASTM D-635 self-extinguishing
Separator Microporous with fibrous glass mat
Safety vent system Flame-arrester type with dust cover
Terminals
4LCY/LY-290 and 420
4LCY/LY-544 and 660
Two, 0.5-in (12.7 mm) x 1.38 in (35.1 mm) cast-lead terminals
Two, 1-in (25 mm) square posts per unit
Withdrawal tubes One per cell
Options
Container
Transparent, flame-retardant polycarbonate.
Flammability ratings: UL 94-HB; ASTM D-635 self-extinguishing
Special voltages Modules with dummy cells are available


 

Final volts
Models
Nominal rates at 77F (25C) (includes connector voltage drop) Amperes per cell
24 Hr
12 Hr
8 Hr
5 Hr
3 Hr
2 Hr
1 Hr
1.88
LCY/LY-290
LCY/LY-420
LCY/LY-544
LCY/LY-660
14
19
24
28

22
32
41
50

29
42
55
66
40
58
75
91
  52
  76
102
122
  67
  97
125
155
  89
129
168
207
1.86
LCY/LY-290
LCY/LY-420
LCY/LY-544
LCY/LY-660
14
20
25
29
23
33
43
53
31
45
58
70
43
62
80
97
  57
  82
111
133
  72
105
136
168
  98
144
186
230
1.84
LCY/LY-290
LCY/LY-420
LCY/LY-544
LCY/LY-660
13
19
25
31
24
34
45
54
33
47
61
74
  44
  64
  83
101
  60
  87
116
140
  77
113
146
180
107
156
202
250
1.75
LCY/LY-290
LCY/LY-420
LCY/LY-544
LCY/LY-660
15
21
27
33
27
38
50
60
36
53
68
83
  51
  73
  95
115
  73
105
136
165
  97
140
181
220
145
210
272
330
Note:

Rates shown represent average values and are subject to IEEE-485 (6.2.4.).


 

 
Type of cell
(CPR code number)
Cells
per
unit
Plates
per
cell
Nominal rates
at 77F(25C)
(includes connector
voltage drop)
Ampere-hours
@ 1.75 F.V.
Overall dimensions
Approx. wt.
lbs (kgs)
Electr-
olyte
per
cell
lbs
(kgs)
Pure
sulfuric
acid
per
cell
lbs
(kgs)
Calcium
Antimony
8 Hr
5 Hr
3 Hr
1 Hr
L in
(mm)
W in
(mm)
H in
(mm)
Net
filled
Dom.
packed
4LCY-290
(164422)
4LY-290
4
5
290
253
218
145
10.08
(256)
 
 
253
(114.8)
268
(121.6)
20
(9.1)
6.0
(2.7)
4LCY-420
(162232)
4LY-420
4
7
420
366
315
210
10.08
(256)
14.12
(359)
22.75
(578)
310
(140.6)
325
(147.4)
18
(8.2)
5.4
(2.4)
4LCY-544
4LY-544
4
9
544
474
408
272
15.00
(381)
395
(179.2)
415
(188.2)
25
(11.3)
7.5
(3.4)
4LCY-660
(164423)
4LY-660
4
11
660
575
495
330
15.00
(381)
 
 
450
(204.1)
470
(213.2)
23
(10.4)
6.9
(3.1)
Notes: 1. Electrolyte weighs approximately 10 lbs per gallon (1.210 kgs per liter).
 
 

 

 
 